TRP-C28
You are here: The Debug Store > Automation > Automation Interfaces > ModBus > Trycom > TRP-C28
|
* Wide input range DC power supply * Support ASCII and Modbus RTU protocol * Supports baud rates from 1.2Kbps to 115.2 Kbps * All 4 channels digital input ca be used as counter * Digital input signal with 3750Vrms isolation protection * Dual watchdog: Modules firmware, host computer traffic * LED for each channels working status * DIN rail and panel mount support * Configured and self-test by outer dip-switch * Support screw terminal and external DC power adaptor |
|
* Input channel: 4 digital input channels * Input optical isolation: 3750 Vrms * Input logical level 0 +1/-V (max) * Input logical level 1 +/-4.0V ~ +/-30V * Digital output Maximum voltage: +/-30V * Communication interface: RS-485 * Communication speed: Baud rate from .2kbps to 115.2Kbps * Input impedance: 3Kohm * Distance: 500M (max) * Digital Input can be used as counter channel: 4 * Counter frequency: 100Hz * Output channel: 4 channel power reply outputs * Relay type: 2 Form A (RL1,RL2) , 2 Form C (RL3,RL4) * Contact ratting: 5A /30V DC , 5A /120V AC , 5A /250V AC * Relay surge strength: 4000V * Relay operating time: 3mS * Relay operating life: 2 X 10(7) * Dual watchdog: Hardware reset circuit, module and host operating status * Signal LED: Power on, all channels * Power supply: Screw terminal, or external DC adapter * Connection type: Screw terminal, accepts AWG #12~320 wires * Power consumption: 2.7W * Operating environment: -10 to 50 deg C * Storage temperature: -20 to 70 deg C * Humidity: 10-90% Non-condensing * Dimension: 151mm X 75mm X 26mm * Weight: 400g |
|
You are here: The Debug Store > Automation > Automation Interfaces > ModBus > Trycom > TRP-C28