TRP-C29U
You are here: The Debug Store > Automation > Automation Interfaces > ModBus > Trycom > TRP-C29U
|
* Powered from USB port * System get a seriall com port when USB plug in * Support ASCII and Modbus RTU protocol * Supports baud rates from 1.2Kbps to 115.2 Kbps * All 8 channels digital input ca be used as counter * Digital input signal with 3750Vrms isolation protection * Dual watchdog: Modules firmware, host computer traffic * LED for each channels working status * DIN rail and panel mount support * Configured and self-test by outer dip-switch * Support screw terminal |
|
* Built-in USB 2.0 to serial bridge * Input channel: 8 digital input channels * Input optical isolation: 3750 Vrms * Input logical level 0 +/-1V (max) * Input logical level 1 +/-4.0V ~ +/-30V * Digital Input can be used as counter channel:8 * Input counter :Dec 0~65535(max) or Hex 0000~FFFF(max) * Input impedance: 3Kohm * Input Counter frequency: 100Hz * Input distance: 500M (max) * Output Maximum voltage: +/-30V * Output Maximum current: 100 mA * Digital output isolation: 3750Vrms * Communication interface: USB * Communication speed: Baud rate from 1.2kbps to 115.2Kbps * Dual watchdog: Hardware reset circuit, module and host operating status * Signal LED: Power on, all channels * Power supply: Directly input from USB * Connection type: Screw terminal, accepts AWG #12~32 wires * Power consumption: 1.2W * Operating environment: -10 to 50 deg C * Storage temperature: -20 to 70 deg C * Humidity: 10-90% Non-condensing * Dimension: 151mm X 75mm X 26mm * Weight: 400g |
|